Upcoming PLC end-of-life milestones

Important deadlines for maintenance teams planning purchases, holding spares or migration work. Always check the exact manufacturer part number.

Lifecycle terms explained

A date labelled “discontinued” does not mean equipment stops working — or even that every repair service is gone.

Active

Manufacturer currently lists the exact product as active. Check its variant and series.

End-of-life announced

A future manufacturer milestone has been published; order and shipping dates may differ.

Spares only

New projects are no longer the intended use, but the OEM may supply spares for existing systems.

Discontinued

Product is no longer generally sold new. Repair and exchange may still exist for some SKUs.

Siemens lifecycle correction: PM410 means product cancellation / spares phase. PM490 means product discontinuation; PM500 means the end of the product lifecycle. PM490 and PM500 must not be combined as if they were the same status. Rockwell “End of Life” often refers to a future discontinuation date, not an expired repair service.

Find your PLC family

Search exact identifiers such as 1747-L552, 6ES7, CJ2M-CPU31 or Q06UDEH. Model-level status can differ within a family.

35 manufacturer-linked records shown.

SiemensSiemens SIMATIC S5 (6ES5)References reviewed: 8 Oct 2026Discontinued / legacy

End of life cycle: no Siemens spares or repairs

  • Lifecycle status: End of life cycle: no Siemens spares or repairs
  • Last order / production: not published
  • Support / repairs: Life cycle ended 30 Sep 2020; no spares or repairs from Siemens since then
  • Successor / migration: Current Siemens range, e.g. S7-1500 (Siemens names no one-for-one replacement)

Source document ↗

Read related AO lifecycle guide ↗

Always check the exact part number and hardware revision.

SiemensSiemens SIMATIC S7-400References reviewed: 8 Oct 2026Active / listed

CPUs active; central I/O spares-only from 1 Oct 2026

  • Lifecycle status: CPUs active; central I/O spares-only from 1 Oct 2026
  • Last order / production: Central I/O: new parts until 1 Oct 2026
  • Support / repairs: Central I/O: PM490 not planned before Oct 2035. CPUs: Siemens states availability beyond 2035
  • Successor / migration: I/O: ET 200MP, ET 200SP or ET 200SP HA. CPUs stay current (S7-410 for PCS 7)

Source document ↗ · Additional reference ↗

Always check the exact part number and hardware revision.

SiemensSiemens SIMATIC ET 200SReferences reviewed: 8 Oct 2026Spares only

Discontinued: spare parts only (PM410)

  • Lifecycle status: Discontinued: spare parts only (PM410)
  • Last order / production: New parts until 1 Oct 2023
  • Support / repairs: Not published as a single date (Siemens policy: PM490 not before 10 years after PM400)
  • Successor / migration: ET 200SP

PM400 date (1 Oct 2020) is from Siemens partner posts, not the Siemens notice read.

Source document ↗ · Additional reference ↗

Always check the exact part number and hardware revision.

SiemensSiemens SIMATIC ET 200SP / ET 200MPReferences reviewed: 8 Oct 2026Active / listed

Active

  • Lifecycle status: Active
  • Last order / production: not published
  • Support / repairs: not published
  • Successor / migration: n/a (current range)

Source document ↗ · Additional reference ↗

Always check the exact part number and hardware revision.

Allen-BradleyAllen-Bradley MicroLogix 1000 (1761)References reviewed: 8 Oct 2026Discontinued / legacy

Discontinued

  • Lifecycle status: Discontinued
  • Last order / production: not published
  • Support / repairs: Not published
  • Successor / migration: Micro800 (Rockwell MicroLogix to Micro800 modernisation guide)

Source document ↗ · Additional reference ↗

Read related AO lifecycle guide ↗

Always check the exact part number and hardware revision.

Allen-BradleyAllen-Bradley MicroLogix 1200 (1762)References reviewed: 8 Oct 2026Discontinued / legacy

Discontinued

  • Lifecycle status: Discontinued
  • Last order / production: not published
  • Support / repairs: Not published
  • Successor / migration: Micro800

Source document ↗

Read related AO lifecycle guide ↗

Always check the exact part number and hardware revision.

Allen-BradleyAllen-Bradley MicroLogix 1400 (1766)References reviewed: 8 Oct 2026Active / listed

Active Mature

  • Lifecycle status: Active Mature
  • Last order / production: not published
  • Support / repairs: not published
  • Successor / migration: Micro800 (Rockwell lists a replacement)

Source document ↗

Read related AO lifecycle guide ↗

Always check the exact part number and hardware revision.

Allen-BradleyAllen-Bradley MicroLogix 1500 (1764)References reviewed: 8 Oct 2026Discontinued / legacy

Discontinued

  • Lifecycle status: Discontinued
  • Last order / production: not published
  • Support / repairs: Not published
  • Successor / migration: Micro800 or CompactLogix

Source document ↗

Read related AO lifecycle guide ↗

Always check the exact part number and hardware revision.

Allen-BradleyAllen-Bradley CompactLogix 1769-L3xReferences reviewed: 8 Oct 2026Discontinued / legacy

Discontinued

  • Lifecycle status: Discontinued
  • Last order / production: not published
  • Support / repairs: Not published
  • Successor / migration: CompactLogix 5370 or 5380

Source document ↗

Always check the exact part number and hardware revision.

Schneider ElectricModicon Premium (TSX)References reviewed: 20 Oct 2026Discontinued / legacy

Discontinued: service only

  • Lifecycle status: Discontinued: service only
  • Last order / production: End of active sale 31 Dec 2018 (per Schneider notice reported by partners); se.com shows e.g. TSXP573634M and TSXAEY414 discontinued 2 Dec 2020
  • Support / repairs: End of standard service 31 Dec 2026 (se.com product pages)
  • Successor / migration: Modicon M580 / Modicon X80 I/O (se.com names e.g. BMXART0414 for TSXAEY414)

Dates vary by reference.

Source document ↗ · Additional reference ↗

Read related AO lifecycle guide ↗

Always check the exact part number and hardware revision.

Schneider ElectricModicon Quantum (140)References reviewed: 20 Oct 2026Discontinued / legacy

End of commercialisation: dates per reference

  • Lifecycle status: End of commercialisation: dates per reference
  • Last order / production: Selected 140 I/O ended 31 Dec 2021; remaining references removed from active sale 31 Dec 2022, obsolescence 15 Jan to 31 Dec 2023 (Schneider notice). Some 140 I/O still orderable to 31 Dec 2030 per se.com
  • Support / repairs: Per reference: e.g. 140CPU43412UC ended 8 Oct 2025; others 31 Dec 2026 to 31 Dec 2030
  • Successor / migration: Modicon M580 (Quantum Ethernet I/O / X80)

Always check the exact 140 reference; C (coated) versions have different dates.

Source document ↗ · Additional reference ↗

Read related AO lifecycle guide ↗

Always check the exact part number and hardware revision.

GE Fanuc / EmersonGE Fanuc Series 90-30 (IC693)References reviewed: 20 Oct 2026Discontinued / legacy

Discontinued: production ended

  • Lifecycle status: Discontinued: production ended
  • Last order / production: Emerson sold remaining factory inventory until 30 Sep 2020 (Emerson notice, Aug 2020)
  • Support / repairs: Not published
  • Successor / migration: PACSystems RX3i (IC695/IC694)

The often quoted "discontinued 1 Oct 2017" date is from resellers, not Emerson: not used.

Source document ↗ · Additional reference ↗

Read related AO lifecycle guide ↗

Always check the exact part number and hardware revision.

GE Fanuc / EmersonPACSystems RX3i CPU310 / CPU315 / CPU320References reviewed: 20 Oct 2026Discontinued / legacy

Discontinued

  • Lifecycle status: Discontinued
  • Last order / production: Mature from 1 May 2015 (GE bulletin T-15-04-01); now listed Discontinued in Emerson CPU manual
  • Support / repairs: Not published
  • Successor / migration: CPU310 > CPE310; CPU315 > CPE310 or CPE330; CPU320 > CPE330

Source document ↗ · Additional reference ↗

Read related AO lifecycle guide ↗

Always check the exact part number and hardware revision.

GE Fanuc / EmersonPACSystems RX3i platform (IC695/IC694), incl. CPE302/305/310/330References reviewed: 20 Oct 2026Active / listed

Active platform (CPE302/305/310/330 Active); individual modules vary

  • Lifecycle status: Active platform (CPE302/305/310/330 Active); individual modules vary
  • Last order / production: Not published
  • Support / repairs: Not published
  • Successor / migration: n/a (current range)

Emerson lifecycle spreadsheet (KBA000083225) needs a login, so module-level status was not checked.

Source document ↗ · Additional reference ↗

Read related AO lifecycle guide ↗

Always check the exact part number and hardware revision.

GE Fanuc / EmersonVersaMax Micro (IC200U)References reviewed: 20 Oct 2026Active / listed

Still listed by Emerson (no discontinuation notice found)

  • Lifecycle status: Still listed by Emerson (no discontinuation notice found)
  • Last order / production: Not published
  • Support / repairs: Not published
  • Successor / migration: Emerson positions PACSystems RSTi-EP / RX3i for new designs (not an official like-for-like)

Source document ↗

Read related AO lifecycle guide ↗

Always check the exact part number and hardware revision.

FANUCFANUC Alpha (non-i) servo motors and amplifiers (A06B)References reviewed: 20 Oct 2026Verify status

Unverified: superseded by Alpha i / Beta i; FANUC publishes no dated end-of-life

  • Lifecycle status: Unverified: superseded by Alpha i / Beta i; FANUC publishes no dated end-of-life
  • Last order / production: Not published
  • Support / repairs: FANUC states lifetime support for its products (contact FANUC service)
  • Successor / migration: FANUC Alpha i / Alpha i-B series

Do not publish a status; show "ask us".

Source document ↗ · Additional reference ↗

Read related AO lifecycle guide ↗

Always check the exact part number and hardware revision.

OmronOmron CJ1 CPUsReferences reviewed: 8 Oct 2026Discontinued / legacy

Discontinued (CPUs)

  • Lifecycle status: Discontinued (CPUs)
  • Last order / production: CJ1G-CPU42P to 45P (Europe): Mar 2025
  • Support / repairs: CJ1G/CJ1H: 7 years' repairs promised (to around 2019). CJ1G-CPU4xP: 7 years after final order
  • Successor / migration: CJ2M / CJ2H (CJ2M itself is being replaced by CJ3M)

Source document ↗ · Additional reference ↗

Always check the exact part number and hardware revision.

OmronOmron CQM1 / CQM1HReferences reviewed: 8 Oct 2026Discontinued / legacy

Discontinued; repair period over

  • Lifecycle status: Discontinued; repair period over
  • Last order / production: not published
  • Support / repairs: Omron promised repairs for 7 years, so to around Mar 2019
  • Successor / migration: CJ2M (now CJ3M)

Omron's own notice, read from a third-party copy; Omron's site did not serve it.

Source document ↗

Always check the exact part number and hardware revision.

OmronOmron NJ / NXReferences reviewed: 8 Oct 2026Active / listed

Active

  • Lifecycle status: Active
  • Last order / production: not published
  • Support / repairs: not published
  • Successor / migration: n/a (current range)

Source document ↗

Always check the exact part number and hardware revision.

SiemensSIMATIC S7-300 / ET 200M6ES7 3xx, 6ES7 15x, ET 200M; confirm individual MLFBSpares only

Existing installations are in the spares-only phase, not automatically unsupported.

PM410: spares-only
1 Oct 2025
PM490: discontinuation
Planned from Oct 2033; exceptions apply
Replacement direction
S7-1500 / ET 200SP; engineering assessment required

What this means: Siemens documentation describes spares availability after product cancellation. PM490 is not the same as PM500: it must not be presented as a definite end to all support. Some subcomponents had earlier deadlines.

SiemensSIMATIC S7-1200 first generation (G1)S7-1200 G1 CPUs and modules; 6ES7 21x / 22x variantsEnd-of-life announced

Siemens has announced the phase-out of the first-generation platform.

Phase-out announcement takes effect
1 Nov 2026
Final order for your MLFB
Check Siemens notice / product record
Successor platform
SIMATIC S7-1200 G2

What this means: The G1 family is not being switched off in November 2026. Check your individual product number for ordering and availability; the G2 platform requires compatibility planning.

Allen-BradleySLC 500 — SLC 5/05 CPU1747-L552 (example); 1747-L53x / L54x / L55x need part-specific checksDiscontinued

The 1747-L552 processor is discontinued, with repair options potentially available.

1747-L552 discontinued
31 Mar 2024
Repair or exchange
Check availability with Rockwell
Modernisation
ControlLogix or CompactLogix design review

What this means: The dated evidence relates to catalog number 1747-L552. Do not assume every SLC 500 module shares this date. Software, networking and I/O strategy matter when migrating.

Allen-BradleyPLC-5 Ethernet processor1785-L80E; PLC-5 model-specific lifecycle variesDiscontinued

The 1785-L80E PLC-5 processor is discontinued.

1785-L80E discontinued
31 Jul 2017
Repair services
Rockwell lists repair services; enquire for exact unit
Migration
Engineering replacement, not a direct drop-in

What this means: The PLC-5 system is legacy hardware. Photograph the exact 1785 number and series before arranging critical spares or upgrades.

Allen-BradleyFLEX I/O ControlNet adapter1794-ACNR15End-of-life announced

Rockwell has announced an October 2026 discontinuation date for this adapter.

Discontinuation date
31 Oct 2026
Replacement category
Engineering replacement
Confirm
Exact series and connected network

What this means: Do not treat this as discontinuation of every FLEX I/O module. ControlNet architecture affects replacement choices.

Allen-BradleyFLEX I/O EtherNet/IP adapter1794-AENTEnd-of-life announced

The 1794-AENT is marked End of Life with a published 2028 discontinuation date.

Discontinuation date
30 Sep 2028
Rockwell named replacement
1794-AENTR
Migration
Check rack, network and device compatibility

What this means: An announced discontinuation date is not the same as an immediate cessation of supplies. Confirm availability before a last-time buy.

Allen-BradleyPOINT I/O DeviceNet adapter1734-ADNEnd-of-life announced

The DeviceNet adapter has a published discontinuation date at the end of 2026.

Discontinuation date
31 Dec 2026
Rockwell replacement
No planned Rockwell replacement listed
Action
Review DeviceNet dependencies and spare adapter stock

What this means: This is specific to 1734-ADN; other POINT I/O network adapters can be active.

Allen-BradleyPOINT I/O EtherNet/IP adapter1734-AENTActive

The 1734-AENT product page currently labels this adapter Active.

Rockwell lifecycle
Active at date checked
Discontinuation
No date shown on cited product page
Action
Check series and firmware before purchase

What this means: This is not a blanket statement for every 1734 adapter or module: the DeviceNet 1734-ADN entry has a separate EOL date.

MitsubishiMELSEC-Q Universal model QCPUQ03UDCPU, Q03UDECPU, Q04UDHCPU, Q04UDEHCPU, Q06UDHCPU, Q06UDEHCPU, Q10UDHCPU, Q10UDEHCPU, Q13UDHCPU, Q13UDEHCPU, Q20UDHCPU, Q20UDEHCPU, Q26UDHCPU, Q26UDEHCPUEnd-of-life announced

The listed Universal QCPUs have passed their global order deadline; production ends in October 2026.

Global last-order date
30 Sep 2026 (passed)
Production discontinuation
30 Oct 2026
Repair support listed through
31 Oct 2033

What this means: Mitsubishi bulletin FA-A-0418-A applies to the specifically named QnUD / QnUDE / QnUDH / QnUDEH CPUs. High-speed QnUDV and other Q modules are not automatically covered by this earlier deadline. Mitsubishi suggests QnUDV or iQ-R alternatives subject to compatibility.

MitsubishiMELSEC-Q remaining modelsQnUDV and selected Q-series CPUs, I/O and communications; check bulletin model tableEnd-of-life announced

A later bulletin announces further MELSEC-Q discontinuations for 2029.

Planned order deadline
30 Sep 2029 for listed models
Planned production end
31 Dec 2029 for listed models
Precise applicability
Check FA-A-0495-A and any model exceptions

What this means: The 2029 programme is not a single blanket rule for every Q-series SKU: earlier bulletins already discontinue some processors and modules. Identify your exact model from the bulletin.

MitsubishiMELSEC-F FX3G / FX3GCFX3G, FX3GC (model and region dependent)End-of-life announced

Mitsubishi lists production discontinuation in December 2026.

Global order acceptance
Until Jun 2026 (month published)
Production discontinuation
Dec 2026
Migration direction
MELSEC iQ-F FX5 family — verify compatibility

What this means: The manufacturer publishes the global order month rather than an exact last day here. Regional distributors can use different deadlines, so do not assume new stock is available.

MitsubishiMELSEC-F FX3U / FX3UCFX3U and FX3UC main units plus listed extensionsEnd-of-life announced

The high-functionality FX3U family has a published March 2028 global order cut-off.

Order acceptance until
31 Mar 2028
Production discontinuation
30 Sep 2028
Repair support planned through
30 Sep 2035; individual exceptions apply

What this means: Mitsubishi bulletin FAM-A-0116-B notes exceptions, including some items with shorter repair periods. Check local UK / EU last-time-buy arrangements rather than assuming the global date guarantees regional ordering.

MitsubishiMELSEC-L systemL02CPU, L06CPU, L26CPU, LX / LY I/O, LJ communications; model exceptions applyEnd-of-life announced

Many MELSEC-L models have a global order deadline in September 2027.

Global order acceptance
30 Sep 2027 on listed models
Production discontinuation
29 Oct 2027 on listed models
Repair support on listed models
31 Oct 2034

What this means: Mitsubishi also shows earlier dates for certain MELSEC-L modules. Check the exact CPU or I/O number, rather than applying these dates to all L-series hardware.

OmronCJ2M — CPU3x (EtherNet/IP)CJ2M-CPU31, CPU32, CPU33, CPU34, CPU35End-of-life announced

Omron plans to retire the CPU3x models and introduce CJ3M successors.

Final order entry
End of Mar 2027
Last shipping
End of Jun 2027
Suggested successor
Corresponding CJ3M-CPU3x (verify implementation)

What this means: The European Omron notice differentiates final order, last shipping and production status; these should not be labelled interchangeably. Confirm the notice for your region and variant.

OmronCJ2M — CPU1xCJ2M-CPU11, CPU12, CPU13, CPU14, CPU15End-of-life announced

European discontinuation is linked to regulatory transition; regional scope matters.

Europe final order entry
End of Jun 2027
Europe last shipping
End of Sep 2027
Suggested successor
Corresponding CJ3M-CPU1x

What this means: Omron states this CPU1x discontinuation is Europe only; do not describe it as worldwide. Check the CE-marking change and installation requirements with Omron.

No matching record. Not seeing your exact part number? Send us a sourcing enquiry and check the manufacturer's current product page.

Scope: This is a curated reference of 15 evidence-backed records, not a complete catalogue of every PLC, module or variant. A family heading does not make every part number subject to the same dates. All sources were reviewed on 8 October 2026; notices can be revised without warning.

What should a maintenance manager do now?

1. Confirm exact hardware

Record CPU, rack, power supply, communications, I/O part numbers and firmware or hardware series.

2. Back up the controls

Keep PLC/HMI projects, parameters, licences and a tested recovery method — not just spare modules.

3. Plan critical stock

Use likelihood of failure, redundancy and procurement lead time to prioritise what to hold.

4. Plan the migration

Review network protocols, safety, I/O and software compatibility before choosing a replacement.

Obsolete controller? We can help.

Automation Outlet is an independent, engineer-run UK supplier of surplus automation spares, sourcing and managed resale services. We are not affiliated with the manufacturers named above.

Need a spare?

Send the exact catalogue number, required quantity and urgency. We will check availability, condition and test history.

Request obsolete part sourcing →

Got surplus PLC stock?

Upgraded machines may leave useful CPUs, I/O or drives in the stores. Ask for a selective outright offer or seller-held consignment.

See managed consignment →
For UK manufacturers: confidential spares-sharing pilot

We are exploring a brokered network to help factories locate slow-moving or obsolete parts. Participating sites do not get direct access to each other's inventory records or business data.

Ask about the private pilot →

Frequently asked questions

Does discontinued mean my PLC will stop working?

No. Lifecycle notices cover manufacturer ordering or support, not the operation of an installed controller. Keep a tested backup, verified programme and recovery plan.

Can I still buy a Siemens S7-300 PLC?

Siemens lists S7-300 and ET 200M as spares-only (PM410) from October 2025. Availability varies by exact 6ES7 order number; the PM490 stage planned from October 2033 is not the same as complete end of support.

Is the Mitsubishi Q series discontinued in 2026?

Only the Universal model QCPU part numbers in bulletin FA-A-0418-A have the September/October 2026 deadlines. Other Q modules have different notices, including a later 2029 programme.

What is the difference between an end-of-order and end-of-repair date?

End-of-order is the deadline to order new manufacturer parts. Production may continue to fill orders; repair services and spares can continue afterwards. Always check each of these dates separately.

Can Automation Outlet help with an obsolete controller?

Yes. Send the exact PLC or module part number for spares sourcing. We also assess selective outright purchases and managed consignment for surplus industrial automation stock.

How reliable are these lifecycle dates?

These entries were reviewed against linked manufacturer information on 8 October 2026. They are a planning guide, not a warranty of availability or technical interchangeability. Check the exact catalogue number and local maker notice before purchasing or redesigning.

✆